Oxygen Probe CarboProbe LT for °C below 600°C (%O2)
Description
For use in flues and boilers, below 600°C The CarboProbe LT is a low temperature heated probe, intended for use in flues and boilers where the temperature of the gases are below 600°C. It incorporates a heater to maintain the sensor at its working temperature, even if the gas is at a much lower temperature.
Main features
- Based on the ZRO2 zirconia oxygen sensor
- Heater sealed in a stainless steel can, isolating it from corrosive flue gases
- Porous stainless steel filter to minimise dust build-up on the sensor
- Gas inlet for calibration gases Purge facility, to clean the filter in-situ
- Modular construction for simple maintenance
- Compact design (diameter of 50mm), allowing installation in small or large flues Integrated K thermocouple, enabling accurate temperature control of the heater
Spécifications
The LT probe requires a separate instrument panel providing power and temperature control for the heater, purge timing and purge gas.
TECHNICAL CHARACTERISTICS
TECHNICAL CHARACTERISTICS | |
Output | 0 to 1200 mv |
Readout impedance | This probe should be used with controlling, recording and indicating instruments having input impedance of 8 megohms or higher |
Accuracy | +- 2 mV in normal operating range |
Response time | Less than 1 second |
Thermocouple | K |
Operating temperature | 700°C (1290°F) |
Available lenghts | 300mm (11.8”), 400mm (15.7”), 500mm (19.7”), 600mm (23.6”), 700mm (27.5”), 800mm (31.5”), 900mm (35.4”), 1000mm (39.4”) |
Reference air | Uncontaminated dry air at maximum rate of 1 l/h |
Cleaning air | Uncontaminated dry air at maximum rate of 300 l/h |
External diameter | 51 mm |